TEMS 3000 Substation Equipment Condition Monitoring System

For the main electrical primary equipment of substation, such as power transformer, circuit breaker, capacitive equipment and GIS, TEMS3000 substation equipment condition monitoring system realizes on-line condition monitoring, which provides basis for maintenance of substation equipment condition.
Product Description

 

1. Product Introduction of The TEMS 3000 Substation Equipment Condition Monitoring System

 

For the main electrical primary equipment of substation, such as power transformer, circuit breaker, capacitive equipment and GIS, TEMS3000 substation equipment condition monitoring system realizes on-line condition monitoring, which provides basis for maintenance of substation equipment condition. TEMU-IM01 Integrated Monitoring Unit and TEMS 3000 Substation Equipment Status Online Monitoring System Software.

 

2. Product Feature And Application of The TEMS 3000 Substation Equipment Condition Monitoring System

 

Product Features:

High Voltage Joint Wireless Temperature Monitoring Devices

Through the micro temperature sensor with automatic wireless networking function, the temperature of the high voltage contacts in the outdoor substation and the switch cabinet is monitored in real time, and the centralized transceiver device is connected to the main station of the system to realize the abnormal warning and alarm of the high voltage contacts and equipment temperature. TSMU-TS01 Wireless Temperature Sensor and TSMU-TM01 Data Terminal.

 

Capacitive Equipment Insulation Monitoring Devices

Used to monitor the insulation performance of capacitive high-voltage electrical equipment, such as transformer core, bushing, voltage transformer, coupling capacitor, oxide arrester, etc., to prevent the failure of high-voltage equipment due to insulation aging and avoid power accidents caused by it. TEMU-IS01/I02 Current Sensor and TEMU-VS01 Voltage Sensor

 

GIS Partial Discharge Monitoring Devices

The UHF (ultra high frequency) on-line monitoring technology is used to monitor and analyze the electromagnetic wave signals of partial discharge inside the gas insulated combined electric appliance (GIS) equipment, so as to monitor and evaluate the operating status of GIS equipment and effectively avoid sudden accidents of GIS high voltage equipment. TEMU-HFS01 UHF Sensor and TEMU-LA01 Data Processing Unit.

 

Transformer Partial Discharge Monitoring Devices

Using UHF (ultra high frequency) on-line monitoring technology, automatic tracking and monitoring of partial discharge level in transformer is carried out according to the set time interval, so as to realize real-time monitoring and evaluation of transformer operation state, and find the hidden trouble in time. TEMU-HFS02 UHF Sensor and TEMU-LA02 Data Processing Unit.
 

Transformer Chromatogram Monitoring Devices

Based on the principle of chromatographic analysis, it can simultaneously detect H2, CO, CO2, CH4, C2H2, C2H4, C2H6 and other full component gases in transformer insulation oil according to the set period, and can assist to realize the real-time detection of moisture in oil. Through the analysis and diagnosis of fault characteristic gas, the transformer fault information can be captured in time and the operation and maintenance of equipment can be guided scientifically.

 

3. Product Details of The TEMS 3000 Substation Equipment Condition Monitoring System

 

 Device Type Product Thumbnail  Device Name And Model The Main Function Main Technical Parameters
'One remote' fault detection system for empty line "One remote" type overhead line fault indicator Elite-AT101

Short circuit and grounding fault detection

Detection of overcurrent and stop power supply

Device self-checking

Local alarm indication

Uploading alarm information

Applicable voltage grade: 6-35kV

Power supply: solar power, rechargeable lithium battery

Communication interface: RADIO frequency (to data terminal)

Alarm indication: number of bowl turns > 5000 times, flash duration > 3000 hours

Reset mode: timing reset, power-on reset, remote reset

Power consumption: static power consumption < 5μA, maximum power < 30mA

Dimensions: 135mm (H) x 110mm (W) x 110mm (D)

Protection level: IP66

"One remote"overhead line fault indicator data terminal Elite-AD10

Receives and processes indicator upload information and forwards it to the master station

SOE event storage

Device self-checking

Power supply: solar power supply, battery

Communication interface: RADIO frequency (for fault indicator, up to 12 rent intervention)

GSM/GPRS (for master station system)

Power consumption: static power consumption < 80μA maximum power < 110mA

Battery capacity: 12AH

Size: 220mm (H) x 200mm (W) x 120mm (D)

Protection level: IP65

'two remote' type overhead line fault detection unit 'Two remote' type overhead line fault indicator Elite-AT102

Short circuit and grounding fault detection

Load current, fault current and wire temperature measurement

Remote parameter modification is supported

Remote control local call and remote call main station

Fifth/seventh harmonic acquisition

Support system timing

Device self-checking

Local alarm indication

Upload measurement data and alarm information

Applicable voltage grade: 6-35kV

Power supply: solar power supply, induction power, rechargeable lithium battery backup

Communication interface: RADIO frequency (to data terminal)

Load current: measuring range 0~1000A; Measurement accuracy: ±2%

Wire temperature: measuring range -40℃~125℃; Measurement accuracy: ±0.5℃

Alarm indication: number of bowl turns > 5000 times, flash duration > 3000 hours

Reset mode: timing reset, power-on reset, remote reset

Power consumption: static power consumption < 20 mu A; Maximum power consumption < 30mA

Dimensions: 135mm (H) x 110mm (W) x 110mm (D)

Protection level: IP66
'Two remote' type overhead line fault indicator data terminal Elite-AD20

Receives and processes indicator upload information and forwards it to the master station

Receives and processes master station instructions and issues them to indicators

Support system timing

SOE time storage

Device self-checking

Power supply: solar power supply, battery

Communication interface: RADIO frequency (for fault indicator, up to 12 rent intervention)

GSM/GPRS (to system master station)

Power consumption: static power consumption < 80μA maximum power < 110mA

Battery capacity: 24AH

Dimensions: 440mm (H) x 400mm (W) x 240mm (D)

Protection level: IP65

 

4. Product Qualification of The TLMS 3000 Transmission Line Condition Monitoring System

 

 

5. Deliver, Shipping And Serving of The TEMS 3000 Substation Equipment Condition Monitoring System

 

Depending on the size of the order and the shipping distance (The usual delivery time is 1 month), and the warranty is 1 year. Besides, the terms of transaction are FOB full payment.

 

6. FAQ

 

Q: What's your lead time?'

A: Generally, the whole production cycle from raw material to finished product takes 15-30 days, but we can ship within 7 days and we can change according to quantity or other conditions as we have raw material stock semi-finished products.

 

Q: Are you a trading company or a manufacturer?

A: We are the original manufacturer, so we have the advantage of price.

 

Q: How long is the product life?

A: Our products are maintenance-free and sealed, using advanced technology, long service life, no problems in normal use.

 

Q: How to use the products?

A: Easy to use, please follow the instructions.

 

Q: Are your products' parameters real?

A: All our parameters are real, maximum quantity, competitive price and long life cycle.

 

Q: Do you have any OEM service?

A: If you purchase a certain quantity, we can also print your logo on the battery case.  

 

Q: What is your MOQ?

A: The minimum order quantity is measured according to the product you order.

 

Q: What are your payment terms?

A: The payment shall be communicated in advance, and the contract shall be drawn up according to the time limit stipulated in the contract.

 

Q: What is your product standardization?

A: First according to The Chinese standard, then according to the international export standard.

 

Q: How long will it take you to provide us with the design?

A: Depending on your design requirements, it depends on how difficult it is.

 

 